Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 2, 2019, 05:46 AM
  • 01 0278_01 0277_01072019_233838.mp4

Date
07/01/2019
W/O
771797
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00219
PipeID
P01326
Time
10:46 PM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5580
Sewer Name
01 STANFORD AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_771797_TV01062_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0278
Downstream MH
01 0277
Dir. of Survey
Downstream
Length Surveyed
331.3 ft.
Total Length
331.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
3122
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 01 0278 to 01 0277
MH: 01 0278MH: 01 0277downstream0 ft. MGO - General Observation - CONNECTIONS AT BOTH 3 AND 9 O' CLOCK AT MH ACTIVE0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. VC - Vermin Cockroach0 ft. AMH - Upstream Manhole, Survey Begins - 01 02780 ft. MWM - Water Mark, 35 %of cross sectional area2.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"64.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"115.5 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS118.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"124.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"126.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"157 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"180.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"208.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"232.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"246.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"259.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"282.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"326.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish329 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - DEBRIS329 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish329 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish331.3 ft. AMH - Downstream Manhole, Survey Ends - 01 0277331.3 ft. MGO - General Observation - CONNECTIONS AT BOTH 3 AND 9 O' CLOCK AT MH ACTIVE

Observation photos (3)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2.8 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (27)

DistanceCodeObservation
115.5DSZDEBRIS
331.3AMH01 0277
126.8TFC
326.5CM
232.5TFC
61.5TFC
282.8TFC
331.3MGOCONNECTIONS AT BOTH 3 AND 9 O' CLOCK AT MH ACTIVE
208.6TFC
0MGOCONNECTIONS AT BOTH 3 AND 9 O' CLOCK AT MH ACTIVE
4.8CM
180.9TF
157TF
0MWL
2.8DAE
2.8DAGS
259.1TF
0VC
246.9TF
0AMH01 0278
329DSZDEBRIS
329DAGS
124.9TF
64.1TFC
329DAE
118.5TF
0MWM

Properties (6)

additional_info
SC378254
custom_field_two
3
customer
LACSD
datetime
2019-07-01T22:46:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false