Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 2, 2019, 07:01 AM
  • 01 0276_01 0243_02072019_011105.mp4

Date
07/02/2019
W/O
771797
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00219
PipeID
P01324
Time
12:01 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5580
Sewer Name
01 STANFORD AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_771797_TV01062_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0276
Downstream MH
01 0243
Dir. of Survey
Downstream
Length Surveyed
3 ft.
Total Length
3 ft.
Structural Index
5
Structural Quick
5100
Structural Rating
5
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 01 0276 to 01 0243
MH: 01 0276MH: 01 0243downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 02760 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTIONS AT BOTH 3 AND 9 O' CLOCK AT MH ACTIVE0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. VC - Vermin Cockroach2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Change2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Change3 ft. H - Hole, from 05 to 07 o'clock, within 8 inches of joint: YES3 ft. MSA - Survey Abandoned - VOID

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Change

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Change

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Change

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Change

Observations (9)

DistanceCodeObservation
3H
2DAE
2DAGS
0AMH01 0276
3MSAVOID
0MWL
0MGOCONNECTIONS AT BOTH 3 AND 9 O' CLOCK AT MH ACTIVE
0MWM
0VC

Properties (6)

additional_info
SC378254
custom_field_two
5
customer
LACSD
datetime
2019-07-02T00:01:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false