Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2019, 07:10 AM
  • 15 0724_15 0723 _21062019_004645.mp4

Date
06/21/2019
W/O
771922
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00616
PipeID
P12617
Time
12:10 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6612
Sewer Name
15 MONROVIA OUTFALL TRUNK
City
MONROVIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
09
Purpose
Routine Assessment
Project
WO_771922_TV15131_JUN2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
15 0724
Downstream MH
15 0723
Dir. of Survey
Downstream
Length Surveyed
164.8 ft.
Total Length
164.8 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole 15 0724 to 15 0723
MH: 15 0724MH: 15 0723downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 07240 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start161.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish161.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish161.6 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish161.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish164.8 ft. AMH - Downstream Manhole, Survey Ends - 15 0723164.8 ft. MGO - General Observation - COCKROACHES AT MH164.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (4)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES AT MH

    164.8 ft. - General Observation - COCKROACHES AT MH

Observations (15)

DistanceCodeObservation
2SAP
164.8AMH15 0723
161.6SSS
164.8MGOCOCKROACHES AT MH
0AMH15 0724
164.8MGOCONNECTION AT MH 3 O'CLOCK
161.6SAP
0MWM
161.6SRV
2DAGS
2SSS
0MGOCONNECTION AT MH 9 O'CLOCK
2SRV
0MWL
161.6DAGS

Properties (6)

additional_info
SC378178
custom_field_two
3
customer
LACSD
datetime
2019-06-21T00:10:25-07:00
documentation
PRO PIPE
is_lateral_inspection
false