Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 14, 2019, 08:26 AM
  • A 0320_A 0319 _14082019_013328.mp4

Date
08/14/2019
W/O
771794
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00325
PipeID
P08230
Time
1:26 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6860
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
RFIR_WO_771794_TV15129_JUN2019
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Width
63 in.
Upstream MH
A 0320
Downstream MH
A 0319
Dir. of Survey
Downstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
4
O&M Quick
5121
O&M Rating
7
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole A 0320 to A 0319
MH: A 0320MH: A 0319downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 03200 ft. MWL - Water Level, 70 %of cross sectional area0 ft. MWM - Water Mark, 80 %of cross sectional area2 ft. MSA - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES2 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES

Observation photos (4)

  • Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

    2 ft. - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
2MSAVIEW OF DOWNLEG OF U/S SIPHON.
2SSS
0AMHA 0320
2DAGS
2SAP
0MWL
0MWM

Properties (7)

additional_info
SC378330
custom_field_two
2
customer
LACSD
datetime
2019-08-14T01:26:51-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
29314