- Date
- 07/10/2019
- W/O
- 771933
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00718
- PipeID
- P15183
- Time
- 9:54 PM
- Certificate
- U-715-07000770
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K6705
- Sewer Name
- 19 ARTESIA-CERRITOS TRUNK
- City
- ARTESIA
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 19
- Page No.
- 04
- Purpose
- Routine Assessment
- Project
- RFIR_WO_771933_TV19059_JUN2019
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 12 in.
- Width
- 12 in.
- Upstream MH
- 19 0214
- Downstream MH
- 19 0213
- Dir. of Survey
- Downstream
- Length Surveyed
- 269.1 ft.
- Total Length
- 269.1 ft.
- Structural Index
- 3
- Structural Quick
- 423I
- Structural Rating
- 164
- O&M Index
- 2
- O&M Quick
- 2N00
- O&M Rating
- 150
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 314
Pipe schematic from manhole 19 0214 to 19 0213 Observation photos (5)

0 ft. - Upstream Manhole, Survey Begins - 19 0214

10.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

49.7 ft. - Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES

185.6 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

215.2 ft. - Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES