Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2019, 09:45 AM
  • 15 0281_15 0280 _21062019_030347.mp4

Date
06/21/2019
W/O
771925
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00591
PipeID
P12204
Time
2:45 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6614
Sewer Name
15 AMAR ROAD TRUNK
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_771925_TV15142_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
15 0281
Downstream MH
15 0280
Dir. of Survey
Downstream
Length Surveyed
353.2 ft.
Total Length
353.2 ft.
Structural Index
3
Structural Quick
5231
Structural Rating
17
O&M Index
2
O&M Quick
432U
O&M Rating
230
Overall Index
2
Overall Quick
Overall Rating
247
Pipe schematic from manhole 15 0281 to 15 0280
MH: 15 0281MH: 15 0280downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 02812 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start78.2 ft. IR - Infiltration Runner, at 09 o'clock, within 8 inches of joint: YES78.2 ft. B - Broken, from 02 to 05 o'clock, within 8 inches of joint: YES79.3 ft. HSV - Hole Soil Visible, at 02 o'clock, within 8 inches of joint: YES80.4 ft. IR - Infiltration Runner, at 03 o'clock, within 8 inches of joint: NO96 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES99.6 ft. FS - Fracture Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES153.8 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start - MINERALS178.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"223.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"260.7 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES278.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"343.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"350.5 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish350.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish353.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0280353.2 ft. MGO - General Observation - COCKROACHES AT MH

Observation photos (10)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Infiltration Runner, at 09 o'clock, within 8 inches of joint: YES

    78.2 ft. - Infiltration Runner, at 09 o'clock, within 8 inches of joint: YES

  • Broken, from 02 to 05 o'clock, within 8 inches of joint: YES

    78.2 ft. - Broken, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Hole Soil Visible, at 02 o'clock, within 8 inches of joint: YES

    79.3 ft. - Hole Soil Visible, at 02 o'clock, within 8 inches of joint: YES

  • Infiltration Runner, at 03 o'clock, within 8 inches of joint: NO

    80.4 ft. - Infiltration Runner, at 03 o'clock, within 8 inches of joint: NO

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    96 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

    99.6 ft. - Fracture Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start - MINERALS

    153.8 ft. - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start - MINERALS

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    260.7 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES AT MH

    353.2 ft. - General Observation - COCKROACHES AT MH

Observations (20)

DistanceCodeObservation
350.5DAZ
0MWM
78.2IR
2DAGS
223.4TFC
353.2AMH15 0280
99.6FS
0MWL
79.3HSV
343.9TFC
353.2MGOCOCKROACHES AT MH
78.2B
278.4TFC
178.2TFC
153.8DAZMINERALS
260.7CL
96CL
350.5DAGS
0AMH15 0281
80.4IR

Properties (6)

additional_info
SC378180
custom_field_two
2
customer
LACSD
datetime
2019-06-21T02:45:47-07:00
documentation
PRO PIPE
is_lateral_inspection
false