Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2019, 08:45 AM
  • B 0408_B 0407 _21062019_020324.mp4

Date
06/21/2019
W/O
771924
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00092
PipeID
P08920
Time
1:45 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6613
Sewer Name
B JOINT OUTFALL B - UNIT 5B
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_771924_TV15053_JUN2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
B 0408
Downstream MH
B 0407
Dir. of Survey
Downstream
Length Surveyed
242.8 ft.
Total Length
242.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole B 0408 to B 0407
MH: B 0408MH: B 0407downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 04082 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COAT THROUGHOUT 40%100.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"156.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"241.3 ft. MGO - General Observation - COCKROACHES AT MH241.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish241.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish242.8 ft. AMH - Downstream Manhole, Survey Ends - B 0407242.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT THROUGHOUT 40%

    2 ft. - General Observation - MAG COAT THROUGHOUT 40%

  • General Observation - COCKROACHES AT MH

    241.3 ft. - General Observation - COCKROACHES AT MH

Observations (14)

DistanceCodeObservation
0MWM
156.6TFC
0MWL
242.8AMHB 0407
2DAGS
241.3MGOCOCKROACHES AT MH
100.6TF
220.8TFC
242.8MGOCONNECTION AT MH 3 O'CLOCK
0AMHB 0408
2SAP
2MGOMAG COAT THROUGHOUT 40%
241.3DAGS
241.3SAP

Properties (6)

additional_info
SC378179
custom_field_two
3
customer
LACSD
datetime
2019-06-21T01:45:54-07:00
documentation
PRO PIPE
is_lateral_inspection
false