- Date
- 05/15/2019
- W/O
- 761818
- Weather
- Dry
- Operator/Surveyor
- E.RUIZ
- Sewer ID
- Z00786
- PipeID
- P26738
- Time
- 2:39 AM
- Certificate
- U-715-07000753
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K6549
- Sewer Name
- 21 TRI-CITIES OUTFALL TRUNK
- City
- POMONA
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 21
- Page No.
- 15
- Purpose
- Routine Assessment
- Project
- WO_761818_TV21081_APR2019
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 22 in.
- Upstream MH
- 21 0593
- Downstream MH
- 21 0592A
- Dir. of Survey
- Downstream
- Length Surveyed
- 168.3 ft.
- Total Length
- 168.3 ft.
- Structural Index
- 3
- Structural Quick
- 413E
- Structural Rating
- 166
- O&M Index
- 2
- O&M Quick
- 2F00
- O&M Rating
- 68
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 234
Pipe schematic from manhole 21 0593 to 21 0592A Observation photos (3)

6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

163.6 ft. - Broken, from 08 to 09 o'clock, within 8 inches of joint: YES

163.7 ft. - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES