Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 28, 2019, 11:29 AM
  • 15 0673_15 0672 _28062019_044132.mp4

Date
06/28/2019
W/O
771928
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00602
PipeID
P12565
Time
4:29 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5583
Sewer Name
15 EL MONTE AVENUE TRUNK
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_771928_TV15208_JUN2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0672
Downstream MH
15 0673
Dir. of Survey
Upstream
Length Surveyed
88.4 ft.
Total Length
88.4 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 15 0672 to 15 0673
MH: 15 0672MH: 15 0673upstream0 ft. MSA - Survey Abandoned - GREASE0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish40.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"86.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start86.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start86.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start88.4 ft. MWL - Water Level, 35 %of cross sectional area88.4 ft. MGO - General Observation - REVERSAL88.4 ft. AMH - Downstream Manhole, Survey Begins - 15 067288.4 ft. MWM - Water Mark, 40 %of cross sectional area88.4 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Survey Abandoned - GREASE

    88.4 ft. - Survey Abandoned - GREASE

Observations (13)

DistanceCodeObservation
88.4MSAGREASE
88.4SAP
2.1SSS
2.1DAGS
0MWL
88.4SSS
47.9TFC
0MGOREVERSAL
0AMH15 0672
2.1SAP
0MWM
88.4DAGS
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH

Properties (6)

additional_info
SC378251
custom_field_two
5
customer
LACSD
datetime
2019-06-28T04:29:25-07:00
documentation
PRO PIPE
is_lateral_inspection
false