Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 28, 2019, 11:11 AM
  • 15 0673_15 0672 _28062019_042200.mp4

Date
06/28/2019
W/O
771928
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00602
PipeID
P12565
Time
4:11 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5583
Sewer Name
15 EL MONTE AVENUE TRUNK
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_771928_TV15208_JUN2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0673
Downstream MH
15 0672
Dir. of Survey
Downstream
Length Surveyed
90.4 ft.
Total Length
90.4 ft.
Structural Index
3
Structural Quick
3C2C
Structural Rating
90
O&M Index
2
O&M Quick
4129
O&M Rating
23
Overall Index
2
Overall Quick
Overall Rating
113
Pipe schematic from manhole 15 0673 to 15 0672
MH: 15 0673MH: 15 0672downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 06730 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH ACTIVE0 ft. VC - Vermin Cockroach0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. MGO - General Observation - MAGNEZIUM H.O COATING THROUGHOUT REACH2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start45.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish90.2 ft. DSZ - Deposits Settled Other, 25 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS90.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish90.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish90.4 ft. MSA - Survey Abandoned - UNKNOWN DEBRIS

Observation photos (4)

  • General Observation - MAGNEZIUM H.O COATING THROUGHOUT REACH

    2 ft. - General Observation - MAGNEZIUM H.O COATING THROUGHOUT REACH

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
2MGOMAGNEZIUM H.O COATING THROUGHOUT REACH
2SSS
0AMH15 0673
45.4DAGS
0MWL
90.2DSZDEBRIS
2DAGS
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH ACTIVE
2SAP
90.4SSS
90.3SAP
90.4MSAUNKNOWN DEBRIS
0VC
0MWM

Properties (6)

additional_info
SC378251
custom_field_two
5
customer
LACSD
datetime
2019-06-28T04:11:17-07:00
documentation
PRO PIPE
is_lateral_inspection
false