Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2019, 09:09 AM
  • 18 0750A_18 0750_06172019_022208.mp4

Date
06/17/2019
W/O
766508
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00706
PipeID
P14604
Time
2:09 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6566
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_766508_TV18103_MAY2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
18 0750A
Downstream MH
18 0750
Dir. of Survey
Downstream
Length Surveyed
209.9 ft.
Total Length
209.9 ft.
Structural Index
5
Structural Quick
5441
Structural Rating
27
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
27
Pipe schematic from manhole 18 0750A to 18 0750
MH: 18 0750AMH: 18 0750downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 0750A0 ft. MWL - Water Level, 25 %of cross sectional area2.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.5 ft. MGO - General Observation - MAGNEZIUM H.O COATING ATTATCHED49.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start49.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish49.4 ft. SMW - Surface Missing Wall, at 03 o'clock, within 8 inches of joint: YES148.6 ft. SMW - Surface Missing Wall, from 02 to 04 o'clock, within 8 inches of joint: YES148.6 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES208.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish208.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish209.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0750209.9 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH

Observation photos (6)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    49.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Missing Wall, at 03 o'clock, within 8 inches of joint: YES

    49.4 ft. - Surface Missing Wall, at 03 o'clock, within 8 inches of joint: YES

  • Surface Missing Wall, from 02 to 04 o'clock, within 8 inches of joint: YES

    148.6 ft. - Surface Missing Wall, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES

    148.6 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
0MWM
2.5SAP
2.5SRV
148.6SMW
209.9AMH18 0750
49.4SRC
2.5MGOMAGNEZIUM H.O COATING ATTATCHED
148.6SAM
0AMH18 0750A
208.3SRC
208.3SAP
0MWL
49.4SRV
49.4SMW
209.9MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH

Properties (6)

additional_info
SC377690
custom_field_two
1
customer
LACSD
datetime
2019-06-17T02:09:52-07:00
documentation
PROPIPE
is_lateral_inspection
false