Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 29, 2016, 01:13 PM
  • 14 0555_14 0554_29022016_051426.mp4

Date
02/29/2016
W/O
552346
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00588
PipeID
P18649
Time
5:13 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3271
Sewer Name
14 35TH STREET WEST TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
14
Purpose
Routine Assessment
Project
WO_552346_TV14042_FEB2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
14 0555
Downstream MH
14 0554
Dir. of Survey
Downstream
Length Surveyed
607.5 ft.
Total Length
607.5 ft.
Structural Index
2
Structural Quick
3U2W
Structural Rating
573
O&M Index
2
O&M Quick
2W00
O&M Rating
242
Overall Index
2
Overall Quick
Overall Rating
815
Pipe schematic from manhole 14 0555 to 14 0554
MH: 14 0555MH: 14 0554downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 05550 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING 90%7.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start606.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish606.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish607.5 ft. AMH - Downstream Manhole, Survey Ends - 14 0554

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0AMH14 0555
0MWL
607.5AMH14 0554
2DAGS
606.2DAGS
0MWM
2MGOMAG COATING 90%
7.8SSS
606.2SSS

Properties (6)

additional_info
SC225495
custom_field_two
5
customer
LACSD
datetime
2016-02-29T05:13:40-08:00
documentation
PRO PIPE
is_lateral_inspection
false