Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2016, 09:49 AM
  • 14 0548_14 0547_01032016_015008.mp4

Date
03/01/2016
W/O
552346
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00588
PipeID
P18640
Time
1:49 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3272
Sewer Name
14 35TH STREET WEST TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
Night
Page No.
14
Purpose
Routine Assessment
Project
WO_552346_TV14042_FEB2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
14 0548
Downstream MH
14 0547
Dir. of Survey
Downstream
Length Surveyed
325.1 ft.
Total Length
325.1 ft.
Structural Index
2
Structural Quick
2L00
Structural Rating
126
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
254
Pipe schematic from manhole 14 0548 to 14 0547
MH: 14 0548MH: 14 0547downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 05480 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CAPPED CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK2 ft. MGO - General Observation - MAG COATING 95%2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start324.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish324.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish325.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0547

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
2MGOMAG COATING 95%
325.1AMH14 0547
0AMH14 0548
0MWM
0MWL
7.1SSS
0MGOCAPPED CONNECTION AT MH 9 O'CLOCK
324.3SSS
2DAGS
324.3DAGS
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK

Properties (6)

additional_info
SC225496
custom_field_two
5
customer
LACSD
datetime
2016-03-01T01:49:47-08:00
documentation
PRO PIPE
is_lateral_inspection
false