Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2016, 09:32 AM
  • 14 0548A_14 0548_01032016_013233.mp4

Date
03/01/2016
W/O
552346
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00588
PipeID
P18641
Time
1:32 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3272
Sewer Name
14 35TH STREET WEST TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
14
Purpose
Routine Assessment
Project
WO_552346_TV14042_FEB2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
14 0548A
Downstream MH
14 0548
Dir. of Survey
Downstream
Length Surveyed
475.1 ft.
Total Length
475.1 ft.
Structural Index
3
Structural Quick
3R2Q
Structural Rating
463
O&M Index
2
O&M Quick
2R00
O&M Rating
190
Overall Index
2
Overall Quick
Overall Rating
653
Pipe schematic from manhole 14 0548A to 14 0548
MH: 14 0548AMH: 14 0548downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 0548A0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK2 ft. MGO - General Observation - MAG COATING 95%2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start474.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish475.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0548475.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK475.1 ft. MGO - General Observation - CAPPED CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWL
2MGOMAG COATING 95%
475.1AMH14 0548
475.1MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWM
475.1MGOCAPPED CONNECTION AT MH 9 O'CLOCK
2DAGS
0AMH14 0548A
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
474.5DAGS

Properties (6)

additional_info
SC225496
custom_field_two
5
customer
LACSD
datetime
2016-03-01T01:32:06-08:00
documentation
PRO PIPE
is_lateral_inspection
false