Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2016, 09:46 AM
  • 14 0534_14 0533_03032016_014716.mp4

Date
03/03/2016
W/O
5523246
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00588
PipeID
P18623
Time
1:46 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3274
Sewer Name
14 35TH STREET WEST TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
11
Purpose
Routine Assessment
Project
WO_552346_TV14042_FEB2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
14 0534
Downstream MH
14 0533
Dir. of Survey
Downstream
Length Surveyed
531.7 ft.
Total Length
531.7 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
2
O&M Quick
2T00
O&M Rating
212
Overall Index
2
Overall Quick
Overall Rating
216
Pipe schematic from manhole 14 0534 to 14 0533
MH: 14 0534MH: 14 0533downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 05340 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3 ft. MGO - General Observation - 90% MAG11.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start530.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish530.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish531.7 ft. AMH - Downstream Manhole, Survey Ends - 14 0533

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    11.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
530.1SSS
0AMH14 0534
0MWL
531.7AMH14 0533
11.8SSS
2DAGS
0MWM
530.1DAGS
3MGO90% MAG

Properties (6)

additional_info
SC225498
custom_field_two
5
customer
LACSD
datetime
2016-03-03T01:46:55-08:00
documentation
PRO PIPE
is_lateral_inspection
false