Wastewater/Activity/PacpInspection/1.0Mar 3, 2016, 07:30 AM
  • 14 0535B_14 0535A_02032016_233129.mp4

Date
03/02/2016
W/O
552346
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00588
PipeID
P18626
Time
11:30 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3274
Sewer Name
14 35TH STREET WEST TRUNK
City
PALMDALE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
11
Purpose
Routine Assessment
Project
WO_552346_TV14042_FEB2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
14 0535B
Downstream MH
14 0535A
Dir. of Survey
Downstream
Length Surveyed
209.1 ft.
Total Length
209.1 ft.
Structural Index
3
Structural Quick
3G2G
Structural Rating
203
O&M Index
2
O&M Quick
2G00
O&M Rating
82
Overall Index
2
Overall Quick
Overall Rating
285
Pipe schematic from manhole 14 0535B to 14 0535A
MH: 14 0535BMH: 14 0535Adownstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 14 0535B0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start207.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish207.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish207.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish209.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0535A209.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    8.5 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MWL
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMH14 0535B
207.6DAGS
209.1AMH14 0535A
3.6SAV
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
8.5SSS
0MWM
207.5SSS
209.1MGOACTIVE CONNECTION AT MH 9 O'CLOCK
207.6SAV
2DAGS

Properties (6)

additional_info
SC225498
custom_field_two
3
customer
LACSD
datetime
2016-03-02T23:30:29-08:00
documentation
PRO PIPE
is_lateral_inspection
false