Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2016, 07:08 AM
  • G 0134_G 0133_20160125_232505.mp4

Date
01/25/2016
W/O
547460
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z01180
PipeID
P25039
Time
11:08 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3125
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
19
Purpose
Routine Assessment
Project
WO_547460_TV01004_JAN2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
36 in.
Upstream MH
G 0134
Downstream MH
G 0133
Dir. of Survey
Downstream
Length Surveyed
322.5 ft.
Total Length
322.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
2
Overall Quick
Overall Rating
124
Pipe schematic from manhole G 0134 to G 0133
MH: G 0134MH: G 0133downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - G 01344.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start315 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish322 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK322.4 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK322.5 ft. AMH - Downstream Manhole, Survey Ends - G 0133

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    4.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
4.4DAGS
0MWL
0MWM
322.5AMHG 0133
315DAGS
322.4MGOLATERAL AT MH 3 OCLOCK
322MGOLATERAL AT MH 9 OCLOCK
0AMHG 0134

Properties (7)

additional_info
SC225512
custom_field_two
4
customer
LACSD
datetime
2016-01-25T23:08:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false
year_laid
20040209