Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 8, 2016, 08:19 AM
  • G 0222_G 0221_20160108_003357.mp4

Date
01/08/2016
W/O
547459
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z01180
PipeID
P22445
Time
12:19 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3110
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
SOUTH GATE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_547459_TV01053_JAN2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
G 0222
Downstream MH
G 0221
Dir. of Survey
Downstream
Length Surveyed
179.3 ft.
Total Length
179.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2F00
O&M Rating
68
Overall Index
2
Overall Quick
Overall Rating
68
Pipe schematic from manhole G 0222 to G 0221
MH: G 0222MH: G 0221downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - G 02222 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start18.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"63.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"101.9 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"174.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish179.1 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 9 O'CLOCK179.3 ft. AMH - Downstream Manhole, Survey Ends - G 0221

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
179.3AMHG 0221
0MWL
179.1MGOCONNECTION AT MANHOLE ACTIVE 9 O'CLOCK
101.9TBA
0MWM
2DAGS
0AMHG 0222
174.5DAGS
63.8TBA
18.2TFA

Properties (7)

additional_info
SC224491
custom_field_two
4
customer
LACSD
datetime
2016-01-08T00:19:06-08:00
documentation
PRO-PIPE
is_lateral_inspection
false
year_laid
19990611