Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 18, 2016, 09:50 AM
  • H 1437_H 1436 _18082016_025127.mp4

Date
08/18/2016
W/O
585476
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01204
PipeID
P16309
Time
2:50 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3568
Sewer Name
H JOINT OUTFALL H - UNIT 8M
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
WO_585476_TV22034_AUG2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
H 1437
Downstream MH
H 1436
Dir. of Survey
Downstream
Length Surveyed
358.5 ft.
Total Length
358.6 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole H 1437 to H 1436
MH: H 1437MH: H 1436downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 14370 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK3.7 ft. MGO - General Observation - MAG COAT 80%34.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"67.8 ft. SAV - Surface Aggregate Visible, from 11 to 03 o'clock, within 8 inches of joint: NO72.3 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO73.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"121.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"161.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"209.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"262.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"273 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"321.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"337.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"353.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"358.6 ft. AMH - Downstream Manhole, Survey Ends - H 1436

Observation photos (2)

  • Surface Aggregate Visible, from 11 to 03 o'clock, within 8 inches of joint: NO

    67.8 ft. - Surface Aggregate Visible, from 11 to 03 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

    72.3 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

Observations (18)

DistanceCodeObservation
321.3TF
72.3SAV
0MWL
209.2TF
0AMHH 1437
121.6TFC
34.3TF
3.7MGOMAG COAT 80%
262.3TF
0MWM
67.8SAV
337.5TF
353.6TF
358.6AMHH 1436
73.6TFC
161.8TF
273TFC
0MGOLATERAL AT MH 9 OCLOCK

Properties (6)

additional_info
SC306151
custom_field_two
4
customer
LACSD
datetime
2016-08-18T02:50:56-07:00
documentation
PROPIPE
is_lateral_inspection
false