Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 19, 2016, 08:32 AM
  • H 1412_H 1411 _19082016_013325.mp4

Date
08/19/2016
W/O
585476
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01204
PipeID
P16283
Time
1:32 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3569
Sewer Name
H JOINT OUTFALL H - UNIT 8M
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
30
Purpose
Routine Assessment
Project
WO_585476_TV22034_AUG2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
H 1412
Downstream MH
H 1411
Dir. of Survey
Downstream
Length Surveyed
166.6 ft.
Total Length
166.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2E00
O&M Rating
62
Overall Index
2
Overall Quick
Overall Rating
62
Pipe schematic from manhole H 1412 to H 1411
MH: H 1412MH: H 1411downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 14120 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK5.3 ft. MGO - General Observation - MAG COAT 80%15.7 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Start36.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"101.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"138.5 ft. LL - Alignment Left, 15 %166.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Finish166.6 ft. AMH - Downstream Manhole, Survey Ends - H 1411

Observations (12)

DistanceCodeObservation
166.6DSZ
0MWM
84.5TFC
0AMHH 1412
166.6AMHH 1411
36.2TFC
101.3TF
138.5LL
0MWL
15.7DSZ
0MGOLATERAL AT MH 9 OCLOCK
5.3MGOMAG COAT 80%

Properties (6)

additional_info
SC306153
custom_field_two
4
customer
LACSD
datetime
2016-08-19T01:32:51-07:00
documentation
PROPIPE
is_lateral_inspection
false