Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 11, 2016, 10:09 AM
  • B 0342_B 0306_20160211_032242.mp4

Date
02/11/2016
W/O
552354
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00086
PipeID
P08817
Time
2:09 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3143
Sewer Name
B JOINT OUTFALL B - UNIT 3A
City
ROSEMEAD, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
21
Purpose
Routine Assessment
Project
WO_552354_TV15103_FEB2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Upstream MH
B 0342
Downstream MH
B 0306
Dir. of Survey
Downstream
Length Surveyed
492.2 ft.
Total Length
492.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2D00
O&M Rating
54
Overall Index
2
Overall Quick
Overall Rating
54
Pipe schematic from manhole B 0342 to B 0306
MH: B 0342MH: B 0306downstream0 ft. MGO - General Observation - JUNCTION STRUCTURE0 ft. MWL - Water Level, 0 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 03427.1 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start36.5 ft. MGO - General Observation - MAGNESIUM H.O. START46.1 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"130 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish138.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"166.9 ft. TFI - Tap Factory Made Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 6", 1"241.3 ft. TFI - Tap Factory Made Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 4", 1"492.2 ft. AMH - Downstream Manhole, Survey Ends - B 0306

Observation photos (4)

  • Deposits Settled Compacted,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    7.1 ft. - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Compacted,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Finish

    130 ft. - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

  • Tap Factory Made Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 6", 1"

    166.9 ft. - Tap Factory Made Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 6", 1"

  • Tap Factory Made Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 4", 1"

    241.3 ft. - Tap Factory Made Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 4", 1"

Observations (12)

DistanceCodeObservation
166.9TFI
130DSC
0MGOJUNCTION STRUCTURE
0MWL
36.5MGOMAGNESIUM H.O. START
7.1DSC
0MWM
241.3TFI
138.9TFA
492.2AMHB 0306
0AMHB 0342
46.1TFA

Properties (6)

additional_info
SC225530
custom_field_two
4
customer
LACSD
datetime
2016-02-11T02:09:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false