Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 22, 2016, 10:29 AM
  • 17 0032_17 0031_22022016_022950.mp4

Date
02/22/2016
W/O
552350
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00668
PipeID
P13755
Time
2:29 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3262
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
06
Purpose
V
Project
WO_552350_TV17001_FEB2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Other
Height
21 in.
Upstream MH
17 0031
Downstream MH
17 0032
Dir. of Survey
Upstream
Length Surveyed
95.2 ft.
Total Length
95.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
312C
O&M Rating
42
Overall Index
2
Overall Quick
Overall Rating
45
Pipe schematic from manhole 17 0031 to 17 0032
MH: 17 0031MH: 17 0032upstream0 ft. RML - Roots Medium Lateral, from 12 to 05 o'clock, 30 %, within 8 inches of joint: YES0 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"0 ft. MSA - Survey Abandoned - DUE TO ROOTS AT LATERAL0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish16.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 65"16.1 ft. RFC - Roots Fine Connection, from 02 to 03 o'clock, within 8 inches of joint: YES83.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"91.2 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES93.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start95.2 ft. MWM - Water Mark, 35 %of cross sectional area95.2 ft. AMH - Downstream Manhole, Survey Begins - 17 003195.2 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (4)

  • Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    4 ft. - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Connection, from 02 to 03 o'clock, within 8 inches of joint: YES

    79.1 ft. - Roots Fine Connection, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Roots Medium Lateral, from 12 to 05 o'clock, 30 %, within 8 inches of joint: YES

    95.2 ft. - Roots Medium Lateral, from 12 to 05 o'clock, 30 %, within 8 inches of joint: YES

  • Survey Abandoned - DUE TO ROOTS AT LATERAL

    95.2 ft. - Survey Abandoned - DUE TO ROOTS AT LATERAL

Observations (12)

DistanceCodeObservation
0MWM
95.2RML
0AMH17 0031
95.2TF
4CM
11.9TFA
2DAGS
79.1TFA
79.1RFC
95.2MSADUE TO ROOTS AT LATERAL
95.2DAGS
0MWL

Properties (6)

additional_info
SC225484
custom_field_two
4
customer
LACSD
datetime
2016-02-22T02:29:28-08:00
documentation
PRO PIPE
is_lateral_inspection
false