- Date
- 02/22/2016
- W/O
- 552350
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00668
- PipeID
- P13754
- Time
- 3:00 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K3262
- Sewer Name
- 17 DISTRICT #17 MAIN TRUNK
- City
- PASADENA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 17
- Page No.
- 06
- Purpose
- Routine Assessment
- Project
- WO_552350_TV17001_FEB2016
- Sewer Type
- GRAVITY
- Material
- Vitrified Clay Pipe
- Shape
- Other
- Height
- 21 in.
- Upstream MH
- 17 0031
- Downstream MH
- 17 0030
- Dir. of Survey
- Downstream
- Length Surveyed
- 349.8 ft.
- Total Length
- 349.8 ft.
- Structural Index
- 2
- Structural Quick
- 2100
- Structural Rating
- 2
- O&M Index
- 2
- O&M Quick
- 322M
- O&M Rating
- 148
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 150
Pipe schematic from manhole 17 0031 to 17 0030 Observation photos (5)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

7.2 ft. - Surface Spalling, from 01 to 02 o'clock, within 8 inches of joint: NO

110.6 ft. - Roots Medium Lateral, from 07 to 11 o'clock, 15 %, within 8 inches of joint: YES

157.2 ft. - Roots Medium Lateral, from 08 to 11 o'clock, 20 %, within 8 inches of joint: YES

157.2 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS