Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 19, 2016, 11:54 AM
  • 17 0033_17 0032_19022016_035528.mp4

Date
02/19/2016
W/O
552350
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00668
PipeID
P13756
Time
3:54 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3261
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
06
Purpose
Routine Assessment
Project
WO_552350_TV17001_FEB2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Other
Height
21 in.
Upstream MH
17 0033
Downstream MH
17 0032
Dir. of Survey
Downstream
Length Surveyed
350.2 ft.
Total Length
350.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3225
O&M Rating
17
Overall Index
2
Overall Quick
Overall Rating
17
Pipe schematic from manhole 17 0033 to 17 0032
MH: 17 0033MH: 17 0032downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 17 00332 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start67.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"151.9 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS156.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"211.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"241.1 ft. RMC - Roots Medium Connection, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES241.1 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS297.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"297.3 ft. RFC - Roots Fine Connection, from 01 to 04 o'clock, within 8 inches of joint: YES311.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"340.9 ft. RMC - Roots Medium Connection, from 01 to 05 o'clock, 5 %, within 8 inches of joint: YES340.9 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"348.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish350.2 ft. AMH - Downstream Manhole, Survey Ends - 17 0032

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    151.9 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Roots Medium Connection, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES

    241.1 ft. - Roots Medium Connection, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    241.1 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Roots Fine Connection, from 01 to 04 o'clock, within 8 inches of joint: YES

    297.3 ft. - Roots Fine Connection, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Roots Medium Connection, from 01 to 05 o'clock, 5 %, within 8 inches of joint: YES

    340.9 ft. - Roots Medium Connection, from 01 to 05 o'clock, 5 %, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    340.9 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (19)

DistanceCodeObservation
340.9RMC
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
348.7DAGS
241.1RMC
2DAGS
297.3TFA
0MWL
151.9TFDROOTS
0MWM
311.1TFA
241.1TFDROOTS
340.9TFD
350.2AMH17 0032
211.8TFA
297.3RFC
156.8TFC
0AMH17 0033
123.2TFC
67.8TFC

Properties (6)

additional_info
SC225483
custom_field_two
4
customer
LACSD
datetime
2016-02-19T03:54:36-08:00
documentation
PRO PIPE
is_lateral_inspection
false