Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 19, 2016, 06:52 AM
  • 17 0039_17 0038_18022016_225532.mp4

Date
02/18/2016
W/O
552350
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00668
PipeID
P13762
Time
10:52 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3261
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
06
Purpose
Routine Assessment
Project
WO_552350_TV17001_FEB2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Other
Height
24 in.
Upstream MH
17 0039
Downstream MH
17 0038
Dir. of Survey
Downstream
Length Surveyed
247.3 ft.
Total Length
247.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3122
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 17 0039 to 17 0038
MH: 17 0039MH: 17 0038downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 17 00392 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start95.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"112.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"152.5 ft. RMC - Roots Medium Connection, from 01 to 03 o'clock, 10 %, within 8 inches of joint: YES152.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS212.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"245.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish247.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK247.3 ft. AMH - Downstream Manhole, Survey Ends - 17 0038

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 01 to 03 o'clock, 10 %, within 8 inches of joint: YES

    152.5 ft. - Roots Medium Connection, from 01 to 03 o'clock, 10 %, within 8 inches of joint: YES

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    152.5 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

Observations (12)

DistanceCodeObservation
245.8DAGS
152.5RMC
212.3TFA
0MWM
112.9TFA
2DAGS
247.3MGOACTIVE CONNECTION AT MH 9 O'CLOCK
95.2TFC
0MWL
152.5TFAROOTS
247.3AMH17 0038
0AMH17 0039

Properties (6)

additional_info
SC225483
custom_field_two
4
customer
LACSD
datetime
2016-02-18T22:52:28-08:00
documentation
PRO PIPE
is_lateral_inspection
false