Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 16, 2016, 09:55 AM
  • 17 0062_17 0061_16022016_021736.mp4

Date
02/16/2016
W/O
552349
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00668
PipeID
P13781
Time
1:55 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3257
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
ALTADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
04
Purpose
Routine Assessment
Project
WO_552349_TV17005_FEB2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Other
Height
18 in.
Upstream MH
17 0061
Downstream MH
17 0062
Dir. of Survey
Upstream
Length Surveyed
242.9 ft.
Total Length
242.9 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
4122
O&M Rating
12
Overall Index
2
Overall Quick
Overall Rating
18
Pipe schematic from manhole 17 0061 to 17 0062
MH: 17 0061MH: 17 0062upstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 12 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 17 00622.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish21.9 ft. RFJ - Roots Fine Joint, from 02 to 03 o'clock, within 8 inches of joint: YESR25.4 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR55.7 ft. RFJ - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR65.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"70.8 ft. RFJ - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR86.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"103.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"223.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"240.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start240.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start242.9 ft. MWM - Water Mark, 50 %of cross sectional area242.9 ft. MWL - Water Level, 15 %of cross sectional area242.9 ft. AMH - Downstream Manhole, Survey Begins - 17 0061

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR

    172.1 ft. - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR

    187.2 ft. - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR

    217.5 ft. - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR

Observations (18)

DistanceCodeObservation
172.1RFJ
242.9MGOACTIVE CONNECTION AT MH 12 O'CLOCK
19TF
221RFJ
2DAGS
240.3DAGS
2SAV
187.2RFJ
139.7TFA
0MWM
217.5RFJ
98TFA
0MWL
156TF
242.9AMH17 0062
240.3SAV
0AMH17 0061
177.5TFC

Properties (6)

additional_info
SC225479
custom_field_two
3
customer
LACSD
datetime
2016-02-16T01:55:18-08:00
documentation
PRO PIPE
is_lateral_inspection
false