Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 30, 2019, 09:04 AM
  • 7_1_1_30052019_021654.mp4

Date
05/30/2019
W/O
766493
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00228
PipeID
P01794
Time
2:04 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6555
Sewer Name
01 WRIGHT ROAD TRUNK
City
BELL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
WO_766493_TV01251_MAY2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 0957
Downstream MH
01 0956
Dir. of Survey
Downstream
Length Surveyed
276 ft.
Total Length
276 ft.
Structural Index
2
Structural Quick
3126
Structural Rating
15
O&M Index
2
O&M Quick
2O00
O&M Rating
160
Overall Index
2
Overall Quick
Overall Rating
175
Pipe schematic from manhole 01 0957 to 01 0956
MH: 01 0957MH: 01 0956downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 09570 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 45 %of cross sectional area5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start90.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES145.1 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start177.1 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES242.8 ft. CS - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES246.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES252.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES262.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: NO274.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: NO274.2 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish274.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish276 ft. MGO - General Observation - CONNECTION IN MH 9 OCLOCK276 ft. MGO - General Observation - CONNECTION IN MH 3 OCLOCK276 ft. AMH - Downstream Manhole, Survey Ends - 01 0956

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    90.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

    242.8 ft. - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    246.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    252.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: NO

    262.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: NO

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: NO

    274.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: NO

Observations (17)

DistanceCodeObservation
0AMH01 0957
276MGOCONNECTION IN MH 9 OCLOCK
145.1DSC
276MGOCONNECTION IN MH 3 OCLOCK
274.2CL
274.2DSC
242.8CS
262.9CL
276AMH01 0956
90.4CL
274.2DAGS
0MWL
177.1CM
5DAGS
246.3CL
0MWM
252.8CL

Properties (7)

additional_info
SC377677
custom_field_two
3
customer
LACSD
datetime
2019-05-30T02:04:52-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid