Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2019, 09:46 AM
  • 16_1_1_21062019_030035.mp4

Date
06/21/2019
W/O
766407
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00349
PipeID
P02987
Time
2:46 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6572
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Railway
Location Code
L
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
V
Project
WO_766407_TV02220_MAY2019
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
02 1416
Downstream MH
02 1415
Dir. of Survey
Downstream
Length Surveyed
38.4 ft.
Total Length
38.4 ft.
Structural Index
3
Structural Quick
3727
Structural Rating
35
O&M Index
2
O&M Quick
4127
O&M Rating
18
Overall Index
2
Overall Quick
Overall Rating
53
Pipe schematic from manhole 02 1416 to 02 1415
MH: 02 1416MH: 02 1415downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14164.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start4.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start4.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start38.4 ft. MGO - General Observation - CAMERA HITTING TOP OF PIPE38.4 ft. MGO - General Observation - MH VISIBLE38.4 ft. MSA - Survey Abandoned - VIEW OF THE DOWNLEG PIPE FROM U/S MH38.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish38.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish38.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.5 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.5 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
4.5SSS
0MWM
38.4MGOCAMERA HITTING TOP OF PIPE
38.4MGOMH VISIBLE
0MWL
4.5DAGS
38.4MSAVIEW OF THE DOWNLEG PIPE FROM U/S MH
38.4SAP
0AMH02 1416
38.4SSS
38.4DAGS
4.5SAP

Properties (6)

additional_info
SC377697
custom_field_two
3
customer
LACSD
datetime
2019-06-21T02:46:49-07:00
documentation
PROPIPE
is_lateral_inspection
false