Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2019, 07:54 AM
  • 5_1_1_20062019_015224.mp4

Date
06/20/2019
W/O
766407
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00349
PipeID
P02966
Time
12:54 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6571
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
WO_766407_TV02220_MAY2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
02 1395
Downstream MH
02 1394
Dir. of Survey
Downstream
Length Surveyed
949 ft.
Total Length
949 ft.
Structural Index
3
Structural Quick
513d
Structural Rating
563
O&M Index
2
O&M Quick
2\00
O&M Rating
292
Overall Index
3
Overall Quick
Overall Rating
855
Pipe schematic from manhole 02 1395 to 02 1394
MH: 02 1395MH: 02 1394downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 13950 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area10.5 ft. MGO - General Observation - MAG COAT THROUGHOUT PIPE11.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start214 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start286.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish291.6 ft. SAP - Surface Aggregate Projecting, from 03 to 09 o'clock, within 8 inches of joint: YES, Start742.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO944.7 ft. SAP - Surface Aggregate Projecting, from 03 to 09 o'clock, within 8 inches of joint: YES, Finish944.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish949 ft. AMH - Downstream Manhole, Survey Ends - 02 1394

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    214 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 03 to 09 o'clock, within 8 inches of joint: YES, Start

    291.6 ft. - Surface Aggregate Projecting, from 03 to 09 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

    742.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

Observations (12)

DistanceCodeObservation
291.6SAP
0AMH02 1395
944.7SAP
286.4SAV
10.5MGOMAG COAT THROUGHOUT PIPE
0MWL
944.7DAGS
11.5SAV
742.7SRV
0MWM
214DAGS
949AMH02 1394

Properties (6)

additional_info
SC377696
custom_field_two
2
customer
LACSD
datetime
2019-06-20T00:54:11-07:00
documentation
PROPIPE
is_lateral_inspection
false