Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2019, 06:38 AM
  • 1_1_1_06052019_235321.mp4

Date
05/06/2019
W/O
761820
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00598
PipeID
P12247
Time
11:38 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6524
Sewer Name
15 BALDWIN PARK TRUNK
City
INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
WO_761820_TV15019_APR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
15 0321
Downstream MH
15 0320
Dir. of Survey
Downstream
Length Surveyed
440 ft.
Total Length
440 ft.
Structural Index
3
Structural Quick
3Q22
Structural Rating
268
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
276
Pipe schematic from manhole 15 0321 to 15 0320
MH: 15 0321MH: 15 0320downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 03210 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 65% MAG COAT FROM 08 TO 04 O'CLOCK, START2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start67.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"140 ft. MGO - General Observation - 75% MAG COAT FROM 08 TO 04 O'CLOCK, CHANGE172.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"269.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"439 ft. MGO - General Observation - 75% MAG COAT FROM 08 TO 04 O'CLOCK, FINISH440 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish440 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish440 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK440 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish440 ft. AMH - Downstream Manhole, Survey Ends - 15 0320

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
439MGO75% MAG COAT FROM 08 TO 04 O'CLOCK, FINISH
0MWM
440DAGS
440SSS
2SSS
2SAP
67.7TFC
2MGO65% MAG COAT FROM 08 TO 04 O'CLOCK, START
440MGOACTIVE CONNECTION AT MH 9 O'CLOCK
2DAGS
0AMH15 0321
0MWL
440SAP
140MGO75% MAG COAT FROM 08 TO 04 O'CLOCK, CHANGE
172.9TFC
440AMH15 0320
269.1TFC
0MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC366244
custom_field_two
2
customer
LACSD
datetime
2019-05-06T23:38:11-07:00
documentation
PRO PIPE
is_lateral_inspection
false