Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 13, 2019, 09:59 AM
  • 13_1_1_13052019_033648.mp4

Date
05/13/2019
W/O
761820
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00598
PipeID
P12259
Time
2:59 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6525
Sewer Name
15 BALDWIN PARK TRUNK
City
BALDWIN PARK
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_761820_TV15019_APR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
15 0333
Downstream MH
15 0331A
Dir. of Survey
Downstream
Length Surveyed
518.2 ft.
Total Length
518.2 ft.
Structural Index
2
Structural Quick
3S2T
Structural Rating
506
O&M Index
2
O&M Quick
2U00
O&M Rating
216
Overall Index
2
Overall Quick
Overall Rating
722
Pipe schematic from manhole 15 0333 to 15 0331A
MH: 15 0333MH: 15 0331Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 03330 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"18.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start18.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"40 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"48 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"143.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"213.6 ft. MGO - General Observation - ABANDONED MH236 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"243.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"329.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"339.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"433 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"440.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"491.1 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS518.1 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish518.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish518.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish518.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish518.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0331A518.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK. CONN @ 3 IS A DROP CONNECTION.

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    18.9 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ABANDONED MH

    213.6 ft. - General Observation - ABANDONED MH

Observations (25)

DistanceCodeObservation
440.9TFC
48TFC
40TFC
2DAGS
213.6MGOABANDONED MH
339.1TFC
491.1DSZDEBRIS
518.1DSZ
518.2AMH15 0331A
329.7TFC
0AMH15 0333
0MWL
518.1SSS
236TFC
433TFC
9TBA
243.1TFC
0MWM
143.6TFC
2SSS
518.2MGOACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK. CONN @ 3 IS A DROP CONNECTION.
518.1SAP
518.1DAGS
18.9SAP
18.9TBA

Properties (6)

additional_info
SC366245
custom_field_two
2
customer
LACSD
datetime
2019-05-13T02:59:37-07:00
documentation
PRO PIPE
is_lateral_inspection
false