Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2019, 07:48 AM
  • 6_1_1_07052019_010916.mp4

Date
05/07/2019
W/O
761820
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00598
PipeID
P12252
Time
12:48 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6524
Sewer Name
15 BALDWIN PARK TRUNK
City
INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
WO_761820_TV15019_APR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
15 0326
Downstream MH
15 0325
Dir. of Survey
Downstream
Length Surveyed
425.4 ft.
Total Length
425.4 ft.
Structural Index
3
Structural Quick
3P2P
Structural Rating
420
O&M Index
2
O&M Quick
412P
O&M Rating
173
Overall Index
2
Overall Quick
Overall Rating
593
Pipe schematic from manhole 15 0326 to 15 0325
MH: 15 0326MH: 15 0325downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 15 03260 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start22.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"91.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"118.4 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"134.3 ft. MGO - General Observation - UNMAPPED MH134.4 ft. MGO - General Observation - POSSIBLE UNKNOWN CONN INSIDE THE MANHOLE @ 03 O'CLOCK178.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"186.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"294 ft. LL - Alignment Left, 5 %378.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"386.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"422.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE422.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish422.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish422.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish425.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0325

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - UNMAPPED MH

    134.3 ft. - General Observation - UNMAPPED MH

  • General Observation - COCKROACHES IN MANHOLE

    422.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (22)

DistanceCodeObservation
118.4TBA
186.8TFC
178.8TFC
0MGOCOCKROACHES IN MANHOLE
294LL
0AMH15 0326
0MWL
91.1TFC
2SSS
386.7TFC
422.9MGOCOCKROACHES IN MANHOLE
22.7TBA
0MWM
134.3MGOUNMAPPED MH
2SAP
134.4MGOPOSSIBLE UNKNOWN CONN INSIDE THE MANHOLE @ 03 O'CLOCK
422.9SAP
2DAGS
422.9DAGS
422.9SSS
425.4AMH15 0325
378.7TFC

Properties (6)

additional_info
SC366244
custom_field_two
2
customer
LACSD
datetime
2019-05-07T00:48:28-07:00
documentation
PRO PIPE
is_lateral_inspection
false