Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 29, 2017, 10:05 AM
  • F 0127_F 0126 _11292017_020607.mp4

Date
11/29/2017
W/O
673962
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00042
PipeID
P10259
Time
2:05 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5232
Sewer Name
F JOINT OUTFALL F - UNIT 6
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
34
Purpose
Routine Assessment
Project
WO_673962_TV02160_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
F 0127
Downstream MH
F 0126
Dir. of Survey
Downstream
Length Surveyed
241.3 ft.
Total Length
241.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2I00
O&M Rating
96
Overall Index
2
Overall Quick
Overall Rating
99
Pipe schematic from manhole F 0127 to F 0126
MH: F 0127MH: F 0126downstream0 ft. AMH - Upstream Manhole, Survey Begins - F 01270 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 11 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start31.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"63.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"86.4 ft. CM - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES214.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"239.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish241.3 ft. AMH - Downstream Manhole, Survey Ends - F 0126241.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    86.4 ft. - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
0AMHF 0127
239.5DAGS
63.8TF
214.6TFA
241.3AMHF 0126
86.4CM
241.3MGOCOCKROACHES IN MANHOLE
0MWL
2DAGS
0MGOACTIVE CONNECTION AT MH 11 O'CLOCK
31.9TFA
0MGOCOCKROACHES IN MANHOLE
0MWM

Properties (6)

additional_info
SC346403
custom_field_two
4
customer
LACSD
datetime
2017-11-29T02:05:53-08:00
documentation
PRO PIPE
is_lateral_inspection
false