Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 28, 2019, 04:24 PM
  • 16 0161_16 0185_8282019_094845.mp4

Date
08/28/2019
W/O
PENDING
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00645
PipeID
P13229
Time
9:24 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8067
Sewer Name
16 ARROYO SECO TRUNK, SECTION 2
City
SOUTH PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
20190828SHO_ARROYO_SECO_TRUNK_SECTION_2
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
16 0185
Downstream MH
16 0161
Dir. of Survey
Upstream
Length Surveyed
147.8 ft.
Total Length
147.8 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 16 0185 to 16 0161
MH: 16 0185MH: 16 0161upstream0 ft. AMH - Upstream Manhole, Survey Ends - MH 01611.6 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish1.6 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish113.3 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - VERY MINOR SPALLING142.3 ft. MGO - General Observation - 25% MAG COAT INTACT144 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start147.8 ft. MWM - Water Mark, 10 %of cross sectional area147.8 ft. AMH - Downstream Manhole, Survey Begins - MH 0185147.8 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (2)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    3.8 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 25% MAG COAT INTACT

    5.5 ft. - General Observation - 25% MAG COAT INTACT

Observations (9)

DistanceCodeObservation
0MWM
3.8SAV
34.5SSSVERY MINOR SPALLING
146.2SSS
146.2SAV
0AMHMH 0185
147.8AMHMH 0161
0MWL
5.5MGO25% MAG COAT INTACT

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-28T09:24:02-07:00
documentation
OBREGON, YOUNG, CASTILLO, RUVALCABA
is_lateral_inspection
false