Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 27, 2019, 07:56 PM
  • 02 1331_02 1330_8272019_132304.mp4

Date
08/27/2019
W/O
0786985
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00238
PipeID
P03855
Time
12:56 PM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8066
Sewer Name
02 BELVEDERE TRUNK
City
EAST LA
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
20190827SHO_BELVEDERE_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
02 1331
Downstream MH
02 1330
Dir. of Survey
Downstream
Length Surveyed
253.6 ft.
Total Length
253.6 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 02 1331 to 02 1330
MH: 02 1331MH: 02 1330downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - MH 13310 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. MGO - General Observation - 25% MAG COAT INTACT2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start86.4 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - VERY MINOR SPALLING90.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"109 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"120.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"180.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"182.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"253.6 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish253.6 ft. AMH - Downstream Manhole, Survey Ends - MH 1330253.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
2MGO25% MAG COAT INTACT
182.5TFA
109TF
120.6TFA
253.6SSS
90.8TFC
0MWL
253.6AMHMH 1330
253.6SAV
86.4SSSVERY MINOR SPALLING
180.3TFC
2SAV
0AMHMH 1331
0MWM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-27T12:56:56-07:00
documentation
OBREGON, YOUNG, RUVALCABA, CASTILLO
is_lateral_inspection
false