- Date
- 06/03/2019
- W/O
- 766543
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00030
- PipeID
- P23531
- Time
- 2:08 AM
- Certificate
- U-715-07000770
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K6557
- Sewer Name
- E JOINT OUTFALL E - UNIT 4
- City
- LOS ANGELES
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 13
- Purpose
- Routine Assessment
- Project
- WO_766543_TV01079_MAY2019
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 30 in.
- Width
- 30 in.
- Upstream MH
- E 0064
- Downstream MH
- E 0164
- Dir. of Survey
- Downstream
- Length Surveyed
- 62.6 ft.
- Total Length
- 62.6 ft.
- Structural Index
- 2
- Structural Quick
- 372A
- Structural Rating
- 45
- O&M Index
- 2
- O&M Quick
- 2A00
- O&M Rating
- 24
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 69
Pipe schematic from manhole E 0064 to E 0164 Observation photos (3)

2.6 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

2.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

23.5 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start