Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 28, 2019, 11:39 AM
  • 15 0186_15 0185 _05282019_043951.mp4

Date
05/28/2019
W/O
766956
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00605
PipeID
P12110
Time
4:39 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6545
Sewer Name
15 FERRIS ROAD TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_766956_TV15249_MAY2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0186
Downstream MH
15 0185
Dir. of Survey
Downstream
Length Surveyed
351.3 ft.
Total Length
351.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2Z00
O&M Rating
266
Overall Index
2
Overall Quick
Overall Rating
269
Pipe schematic from manhole 15 0186 to 15 0185
MH: 15 0186MH: 15 0185downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 01860 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start35.4 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS UNDER WATER38.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"57.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"76.7 ft. RPZ - Repair Other, within 8 inches of joint: YES - LINK PIPE80.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"114.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"121.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"152.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"178.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"185.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"203.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"230.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"249 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"276 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"290.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"301.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"335.2 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES348.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"349.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish349.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish351.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE351.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK351.3 ft. AMH - Downstream Manhole, Survey Ends - 15 0185

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Repair Other, within 8 inches of joint: YES - LINK PIPE

    76.7 ft. - Repair Other, within 8 inches of joint: YES - LINK PIPE

  • Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    335.2 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    351.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (27)

DistanceCodeObservation
35.4DSZDEBRIS UNDER WATER
185.6TFC
57.2TFA
0AMH15 0186
349.6DAGS
152.1TFA
335.2CM
349.6DSZ
114.6TFC
121.6TFC
2DAGS
203.9TFC
0MWM
38.2TFA
351.3MGOCOCKROACHES IN MANHOLE
290.5TFC
76.7RPZLINK PIPE
348.5TFA
351.3MGOACTIVE CONNECTION AT MH 9 O'CLOCK
351.3AMH15 0185
301.6TFC
276TFC
80.4TFA
249TFA
230.8TFA
0MWL
178.4TFA

Properties (6)

additional_info
SC378160
custom_field_two
4
customer
LACSD
datetime
2019-05-28T04:39:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false