Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 22, 2019, 09:48 AM
  • 05 0485_05 0484_8222019_031225.mp4

Date
08/22/2019
W/O
0796503
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00526
PipeID
P05700
Time
2:48 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1251
Sewer Name
05 STRAWBERRY AVENUE TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
20190822MDM_STRAWBERRY_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
05 0484
Downstream MH
05 0485
Dir. of Survey
Upstream
Length Surveyed
27.6 ft.
Total Length
27.6 ft.
Structural Index
2
Structural Quick
3124
Structural Rating
11
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 05 0484 to 05 0485
MH: 05 0484MH: 05 0485upstream0 ft. AMH - Upstream Manhole, Survey Ends - 3:20AM0.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active5.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO8.6 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT13.6 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H16.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE21.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE27.6 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active27.6 ft. AMH - Downstream Manhole, Survey Begins - 3:10AM27.6 ft. MWM - Water Mark, 20 %of cross sectional area27.6 ft. MWL - Water Level, 10 %of cross sectional area27.6 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active

Observation photos (1)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO

    22.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO

Observations (13)

DistanceCodeObservation
19FCSLIGHT
0MGOConn. @ Mh, 3 O' Clock. Active
11.4FCHAIRLINE
27.1MGOConn. @ Mh, 9 O' Clock. Active
0AMH3:10AM
14FCH
0MWM
27.6AMH3:20AM
0MWL
0MGOConn. @ Mh, 9 O' Clock. Active
27.1MGOConn. @ Mh, 3 O' Clock. Active
6FLHAIRLINE
22.1SSS

Properties (6)

custom_field_three
SLIGHT & HAIRLINE FRACTURES
custom_field_two
3
customer
LACSD
datetime
2019-08-22T02:48:54-07:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false