Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 5, 2018, 05:24 AM
  • 02 1328_02 2042_04092018_223632.mp4

Date
09/04/2018
W/O
723786
Weather
Dry
Operator/Surveyor
B. FUGATE
Sewer ID
Z00238
PipeID
P03852
Time
10:24 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5994
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_723786_TV02239_SEP2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1328
Downstream MH
02 2042
Dir. of Survey
Downstream
Length Surveyed
284.9 ft.
Total Length
284.9 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
165
Pipe schematic from manhole 02 1328 to 02 2042
MH: 02 1328MH: 02 2042downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13288.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"35.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"68.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"79.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"139.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"198.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"205.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"230.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"258.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"266.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"284.9 ft. AMH - Downstream Manhole, Survey Ends - 02 2042284.9 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK284.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK284.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK284.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (19)

DistanceCodeObservation
258.4TFC
35.8TB
0MWL
198.2TF
266.4TF
284.9AMH02 2042
79.5TFC
0MWM
0AMH02 1328
284.9MGOCONNECTION AT MH 12 O'CLOCK
284.9MGOCONNECTION AT MH 3 O'CLOCK
230.6TFC
284.9MGOCONNECTION AT MH 9 O'CLOCK
284.9CM
8.6CM
139.9TFC
205.9TF
12.6TF
68.7TFC

Properties (5)

additional_info
SC364808
customer
LACSD
datetime
2018-09-04T22:24:00-07:00
documentation
PROPIPE
is_lateral_inspection
false