Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 5, 2018, 07:31 AM
  • 02 1315_02 1314_05092018_004141.mp4

Date
09/05/2018
W/O
723786
Weather
Dry
Operator/Surveyor
B. FUGATE
Sewer ID
Z00238
PipeID
P03835
Time
12:31 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5994
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_723786_TV02239_SEP2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1315
Downstream MH
02 1314
Dir. of Survey
Downstream
Length Surveyed
266 ft.
Total Length
266 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 1315 to 02 1314
MH: 02 1315MH: 02 1314downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13153.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"54.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"59.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"97.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"117.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"180.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"191.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"203.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"241.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"266 ft. AOC - Drop Connection, Survey Ends - 02 1314266 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (17)

DistanceCodeObservation
191.2TFA
0MGOCONNECTION AT MH 9 O'CLOCK
203.7TF
54.8TFC
0MWM
241.7TFC
266AOC02 1314
3.3CM
97.8TF
59.8TF
266CM
180.9TF
0MWL
100.2TF
0AMH02 1315
117.9TF
5.9TB

Properties (6)

additional_info
SC364808
custom_field_two
3
customer
LACSD
datetime
2018-09-05T00:31:00-07:00
documentation
PROPIPE
is_lateral_inspection
false