Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 20, 2018, 04:39 AM
  • 02 1293_02 1292_10122018_132543.mp4

Date
09/19/2018
W/O
723786
Weather
Dry
Operator/Surveyor
B. FUGATE
Sewer ID
Z00238
PipeID
P03810
Time
9:39 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6109
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_723786_TV02239_SEP2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1293
Downstream MH
02 1292
Dir. of Survey
Downstream
Length Surveyed
330.6 ft.
Total Length
330.7 ft.
Structural Index
3
Structural Quick
413L
Structural Rating
199
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
199
Pipe schematic from manhole 02 1293 to 02 1292
MH: 02 1293MH: 02 1292downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 12930 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start63.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"73.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"83.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"114.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"152.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"154.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"187.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"195.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"198.6 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES201.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"225.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"233.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"236.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"268.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"273.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"279.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"314.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"330.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330.7 ft. AMH - Downstream Manhole, Survey Ends - 02 1292

Observations (24)

DistanceCodeObservation
225.7TFC
233.5TB
198.6FM
195.6TF
314.5TF
0MWL
114.1TF
279.2TF
0AMH02 1293
330.7CM
63.1TFC
187.6TF
273.9TF
201.4TB
330.7AMH02 1292
83.6TF
73.8TFC
4CM
268.6TF
152.2TF
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK
236.1TF
154.7TF

Properties (6)

additional_info
SC364825
custom_field_two
3
customer
LACSD
datetime
2018-09-19T21:39:00-07:00
documentation
PROPIPE
is_lateral_inspection
false