Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 20, 2018, 04:53 AM
  • 02 1292_02 1291_10122018_132824.mp4

Date
09/19/2018
W/O
723786
Weather
Dry
Operator/Surveyor
B. FUGATE
Sewer ID
Z00238
PipeID
P03809
Time
9:53 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6109
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_723786_TV02239_SEP2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1292
Downstream MH
02 1291
Dir. of Survey
Downstream
Length Surveyed
331.6 ft.
Total Length
331.7 ft.
Structural Index
3
Structural Quick
413L
Structural Rating
205
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
205
Pipe schematic from manhole 02 1292 to 02 1291
MH: 02 1292MH: 02 1291downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 12920 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"25.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"65.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"73.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"101.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"103.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"103.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"112.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"114.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"183 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"185.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"195.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"211.7 ft. FM - Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES213.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"228.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"228.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"231.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"234.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"269.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"270.1 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES331.7 ft. AMH - Downstream Manhole, Survey Ends - 02 1291331.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (26)

DistanceCodeObservation
213.3TF
2.9CM
112.2TF
0AMH02 1292
65.8TF
73.9TB
103.6TFC
19.6TF
211.7FM
103.5TB
0MWM
25.1TF
331.7AMH02 1291
331.7CM
0MWL
231.1TFC
195.5TF
228.3TFC
234.3TF
101.3TFC
269.4TF
185.2TF
183TF
114.2TF
228.3TB
270.1FS

Properties (6)

additional_info
SC364825
custom_field_two
3
customer
LACSD
datetime
2018-09-19T21:53:00-07:00
documentation
PROPIPE
is_lateral_inspection
false