Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 3, 2019, 09:20 AM
  • 7_1_1_03052019_023812.mp4

Date
05/03/2019
W/O
761425
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00140
PipeID
P09827
Time
2:20 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6530
Sewer Name
C JOINT OUTFALL C - UNIT 8B
City
HAWAIIAN GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
07
Purpose
Routine Assessment
Project
WO_761425_TV19020_APR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
39 in.
Upstream MH
C 0364
Downstream MH
C 0363
Dir. of Survey
Downstream
Length Surveyed
562.3 ft.
Total Length
562.3 ft.
Structural Index
3
Structural Quick
3U00
Structural Rating
330
O&M Index
2
O&M Quick
3111
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
334
Pipe schematic from manhole C 0364 to C 0363
MH: C 0364MH: C 0363downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 03640 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area10 ft. MGO - General Observation - MAG COAT THROUGHOUT PIPE10 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start199.4 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES208.1 ft. IS - Infiltration Stain, from 10 to 02 o'clock, within 8 inches of joint: YES214.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 10"232 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 10"512.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 10"540.2 ft. LR - Alignment Right, 10 %562.3 ft. AMH - Downstream Manhole, Survey Ends - C 0363562.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • General Observation - MAG COAT THROUGHOUT PIPE

    10 ft. - General Observation - MAG COAT THROUGHOUT PIPE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Stain, from 10 to 02 o'clock, within 8 inches of joint: YES

    208.1 ft. - Infiltration Stain, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
562.3AMHC 0363
562.3SAP
10MGOMAG COAT THROUGHOUT PIPE
208.1IS
199.4ID
0AMHC 0364
0MWL
232TFA
540.2LR
10SAP
214.1TFA
512.1TFA
0MWM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-05-03T02:20:08-07:00
documentation
PROPIPE
is_lateral_inspection
false