Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2019, 08:31 AM
  • 1_1_3_07052019_015608.mp4

Date
05/07/2019
W/O
761425
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00140
PipeID
P09821
Time
1:31 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6532
Sewer Name
C JOINT OUTFALL C - UNIT 8B
City
HAWAIIAN GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
09
Purpose
Routine Assessment
Project
WO_761425_TV19020_APR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
39 in.
Upstream MH
C 0358
Downstream MH
C 0357
Dir. of Survey
Downstream
Length Surveyed
782.3 ft.
Total Length
782.3 ft.
Structural Index
3
Structural Quick
3^00
Structural Rating
459
O&M Index
3
O&M Quick
3200
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
465
Pipe schematic from manhole C 0358 to C 0357
MH: C 0358MH: C 0357downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 03580 ft. MWL - Water Level, 40 %of cross sectional area15 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start15 ft. MGO - General Observation - MAG COAT THROUGHOUT PIPE267.1 ft. IS - Infiltration Stain, at 02 o'clock, within 8 inches of joint: YES762.2 ft. ID - Infiltration Dripper, from 10 to 02 o'clock, within 8 inches of joint: YES772.4 ft. ID - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES779.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish782.3 ft. AMH - Downstream Manhole, Survey Ends - C 0357

Observation photos (5)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    15 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT THROUGHOUT PIPE

    15 ft. - General Observation - MAG COAT THROUGHOUT PIPE

  • Infiltration Stain, at 02 o'clock, within 8 inches of joint: YES

    267.1 ft. - Infiltration Stain, at 02 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, from 10 to 02 o'clock, within 8 inches of joint: YES

    762.2 ft. - Infiltration Dripper, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES

    772.4 ft. - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
782.3AMHC 0357
267.1IS
15SAP
772.4ID
0MWM
0AMHC 0358
762.2ID
0MWL
15MGOMAG COAT THROUGHOUT PIPE
779.9SAP

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-05-07T01:31:34-07:00
documentation
PROPIPE
is_lateral_inspection
false