Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 8, 2019, 04:28 AM
  • 5_1_3_07052019_215537.mp4

Date
05/07/2019
W/O
761425
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00140
PipeID
P09825
Time
9:28 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6533
Sewer Name
C JOINT OUTFALL C - UNIT 8B
City
HAWAIIAN GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
07
Purpose
Routine Assessment
Project
WO_761425_TV19020_APR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
39 in.
Upstream MH
C 0362
Downstream MH
C 0361
Dir. of Survey
Downstream
Length Surveyed
688.7 ft.
Total Length
688.7 ft.
Structural Index
3
Structural Quick
3Z00
Structural Rating
402
O&M Index
3
O&M Quick
4233
O&M Rating
17
Overall Index
3
Overall Quick
Overall Rating
419
Pipe schematic from manhole C 0362 to C 0361
MH: C 0362MH: C 0361downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 03620 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area10 ft. MGO - General Observation - MAG COAT THROUGHOUT PIPE16.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start54.6 ft. IR - Infiltration Runner, at 01 o'clock, within 8 inches of joint: YES127.4 ft. IS - Infiltration Stain, at 01 o'clock, within 8 inches of joint: YES304.4 ft. IS - Infiltration Stain, at 02 o'clock, within 8 inches of joint: YES320.6 ft. IR - Infiltration Runner, at 02 o'clock, within 8 inches of joint: YES336.7 ft. IS - Infiltration Stain, at 02 o'clock, within 8 inches of joint: YES343.5 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES361.2 ft. ID - Infiltration Dripper, from 10 to 02 o'clock, within 8 inches of joint: YES401.5 ft. ID - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES, Start688.7 ft. AMH - Downstream Manhole, Survey Ends - C 0361688.7 ft. ID - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish688.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (10)

  • General Observation - MAG COAT THROUGHOUT PIPE

    10 ft. - General Observation - MAG COAT THROUGHOUT PIPE

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    16.6 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Runner, at 01 o'clock, within 8 inches of joint: YES

    54.6 ft. - Infiltration Runner, at 01 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, at 01 o'clock, within 8 inches of joint: YES

    127.4 ft. - Infiltration Stain, at 01 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, at 02 o'clock, within 8 inches of joint: YES

    304.4 ft. - Infiltration Stain, at 02 o'clock, within 8 inches of joint: YES

  • Infiltration Runner, at 02 o'clock, within 8 inches of joint: YES

    320.6 ft. - Infiltration Runner, at 02 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, at 02 o'clock, within 8 inches of joint: YES

    336.7 ft. - Infiltration Stain, at 02 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    343.5 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, from 10 to 02 o'clock, within 8 inches of joint: YES

    361.2 ft. - Infiltration Dripper, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    401.5 ft. - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
0AMHC 0362
304.4IS
16.6SAP
361.2ID
0MWL
127.4IS
688.7AMHC 0361
688.7ID
401.5ID
0MWM
54.6IR
10MGOMAG COAT THROUGHOUT PIPE
320.6IR
336.7IS
343.5ID
688.7SAP

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-05-07T21:28:25-07:00
documentation
PROPIPE
is_lateral_inspection
false