Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 3, 2019, 08:16 AM
  • 8_1_1_03052019_013333.mp4

Date
05/03/2019
W/O
761425
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00140
PipeID
P09828
Time
1:16 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6530
Sewer Name
C JOINT OUTFALL C - UNIT 8B
City
HAWAIIAN GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
07
Purpose
Routine Assessment
Project
WO_761425_TV19020_APR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
39 in.
Upstream MH
C 0365
Downstream MH
C 0364
Dir. of Survey
Downstream
Length Surveyed
549.1 ft.
Total Length
549.1 ft.
Structural Index
3
Structural Quick
3U00
Structural Rating
324
O&M Index
3
O&M Quick
3221
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
332
Pipe schematic from manhole C 0365 to C 0364
MH: C 0365MH: C 0364downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 03650 ft. MGO - General Observation - INFILTRATION STAIN IN MH5.3 ft. MGO - General Observation - MAG COAT START5.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start265.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, at 10 o'clock, , within 8 inches of joint: YES - AT LATERAL265.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 10"521.6 ft. ID - Infiltration Dripper, from 10 to 02 o'clock, within 8 inches of joint: YES532.2 ft. ID - Infiltration Dripper, at 02 o'clock, within 8 inches of joint: YES545.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish549.1 ft. AMH - Downstream Manhole, Survey Ends - C 0364

Observation photos (5)

  • General Observation - MAG COAT START

    5.3 ft. - General Observation - MAG COAT START

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, at 10 o'clock,  , within 8 inches of joint: YES - AT LATERAL

    265.3 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, at 10 o'clock, , within 8 inches of joint: YES - AT LATERAL

  • Infiltration Dripper, from 10 to 02 o'clock, within 8 inches of joint: YES

    521.6 ft. - Infiltration Dripper, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 02 o'clock, within 8 inches of joint: YES

    532.2 ft. - Infiltration Dripper, at 02 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
545.9SAP
265.3DAEAT LATERAL
0MWL
0MWM
5.3MGOMAG COAT START
532.2ID
265.3TFA
521.6ID
0AMHC 0365
5.3SAP
549.1AMHC 0364
0MGOINFILTRATION STAIN IN MH

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-05-03T01:16:52-07:00
documentation
PROPIPE
is_lateral_inspection
false