Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 19, 2019, 11:33 AM
Date
02/19/2019
W/O
750567
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00039
PipeID
P10198
Time
3:33 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6277
Sewer Name
F JOINT OUTFALL F - UNIT 4
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
WO_750567_TV02238_FEB2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
F 0086
Downstream MH
F 0085
Dir. of Survey
Downstream
Length Surveyed
311.5 ft.
Total Length
311.5 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole F 0086 to F 0085
MH: F 0086MH: F 0085downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 00860 ft. MWL - Water Level, 40 %of cross sectional area10 ft. MGO - General Observation - MAG COAT10 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start49.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"307.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish311.5 ft. AMH - Downstream Manhole, Survey Ends - F 0085

Observations (8)

DistanceCodeObservation
0MWM
311.5AMHF 0085
0AMHF 0086
10MGOMAG COAT
307.9SAP
10SAP
49.9TFA
0MWL

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-02-19T03:33:01-08:00
documentation
PROPIPE
is_lateral_inspection
false