Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2019, 06:11 PM
  • 02 1346A_02 1346_8202019_111340.mp4

Date
08/20/2019
W/O
0786986
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00238
PipeID
P03872
Time
11:11 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8060
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
20190820DF_BELVEDERE_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
02 1346
Downstream MH
02 1346A
Dir. of Survey
Upstream
Length Surveyed
110.4 ft.
Total Length
110.4 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 1346 to 02 1346A
MH: 02 1346MH: 02 1346Aupstream0 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Ends - 11:28 AM1.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish89.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish89.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start89.8 ft. MGP - General Photograph89.8 ft. MMC - Material Change, Vitrified clay pipe91.4 ft. MGP - General Photograph108.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start108.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start110.4 ft. MWM - Water Mark, 20 %of cross sectional area110.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active110.4 ft. AMH - Downstream Manhole, Survey Begins - 11:12 AM110.4 ft. MWL - Water Level, 15 %of cross sectional area110.4 ft. MGO - General Observation - ROACHES @ MH

Observation photos (6)

  • Downstream Manhole, Survey Begins - 11:12 AM

    0 ft. - Downstream Manhole, Survey Begins - 11:12 AM

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    19 ft. - General Photograph

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    20.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    20.6 ft. - General Photograph

  • Material Change, Vitrified clay pipe

    20.6 ft. - Material Change, Vitrified clay pipe

Observations (17)

DistanceCodeObservation
20.6SSS
20.6CM
110.4MGOGREASE THROUGHOUT THE REACH (5%)
0MWM
20.6MGP
110.4MGOROACHES @ MH
19MGP
0MGOConn. @ Mh, 3 O' Clock. Active
110.4AMH11:28 AM
20.6MMC
2SAV
0AMH11:12 AM
2SSS
0MWL
0MGOROACHES @ MH
109.1SAV
109.1CM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-20T11:11:26-07:00
documentation
FRANKLIN, CASTILLO, RUVALCABA
is_lateral_inspection
false