Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2019, 04:55 PM
  • 02 1344_02 1343_8202019_102012.mp4

Date
08/20/2019
W/O
0786986
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00238
PipeID
P03869
Time
9:55 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8060
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
20190820DF_BELVEDERE_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
02 1343
Downstream MH
02 1344
Dir. of Survey
Upstream
Length Surveyed
165.1 ft.
Total Length
165.1 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 02 1343 to 02 1344
MH: 02 1343MH: 02 1344upstream0 ft. AMH - Upstream Manhole, Survey Ends - 10:42 AM0 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)0 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN0 ft. MGO - General Observation - ROACHES @ MH2.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.7 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 60% MAG83 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"135.9 ft. MGP - General Photograph148.9 ft. MGP - General Photograph162.6 ft. MGP - General Photograph163.1 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 60% MAG163.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start165 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN165 ft. MGO - General Observation - ROACHES @ MH165 ft. MWL - Water Level, 30 %of cross sectional area165 ft. MWM - Water Mark, 35 %of cross sectional area165.1 ft. AMH - Downstream Manhole, Survey Begins - 10:17 AM

Observation photos (7)

  • Water Level, 30 %of cross sectional area

    0.1 ft. - Water Level, 30 %of cross sectional area

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 60% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 60% MAG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    2.5 ft. - General Photograph

  • General Photograph

    16.2 ft. - General Photograph

  • General Photograph

    29.2 ft. - General Photograph

  • General Observation - Conn. @ Mh, 9 O' Clock. OPEN

    165.1 ft. - General Observation - Conn. @ Mh, 9 O' Clock. OPEN

Observations (18)

DistanceCodeObservation
165.1AMH10:42 AM
165.1MGOGREASE THROUGHOUT THE REACH (5%)
2.5MGP
29.2MGP
2SZ60% MAG
82.1TFA
0.1MGOConn. @ Mh, 3 O' Clock. OPEN
162.4SSS
0.1MGOROACHES @ MH
0AMH10:17 AM
0.1MWL
165.1MGOPeeling & Flaking Throughout The Reach
16.2MGP
165.1MGOConn. @ Mh, 9 O' Clock. OPEN
165.1MGOROACHES @ MH
2SSS
0.1MWM
162.4SZ60% MAG

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-20T09:55:27-07:00
documentation
FRANKLIN, CASTILLO, RUVALCABA
is_lateral_inspection
false