Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 11, 2018, 05:55 AM
  • 22 0865_22 0864 _10102018_232657.mp4

Date
10/10/2018
W/O
729183
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00803
PipeID
P17232
Time
10:55 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6163
Sewer Name
22 DALTON TRUNK, SECTION 3
City
AZUSA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_729183_TV22158_OCT2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
22 0865
Downstream MH
22 0864
Dir. of Survey
Downstream
Length Surveyed
384.8 ft.
Total Length
384.8 ft.
Structural Index
3
Structural Quick
5E3N
Structural Rating
520
O&M Index
2
O&M Quick
412N
O&M Rating
156
Overall Index
3
Overall Quick
Overall Rating
676
Pipe schematic from manhole 22 0865 to 22 0864
MH: 22 0865MH: 22 0864downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 08650 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0.1 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start18.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"34.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"37.8 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"76.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"84.1 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"84.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"124.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"144.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"228.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"244.1 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES249 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"250.8 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start292.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"300.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"345.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"352.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"383.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish383.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish383.4 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish383.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish384.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0864384.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observations (30)

DistanceCodeObservation
0.1MWM
0AMH22 0865
250.8SRV
195.7TFA
2SAP
144.2TFA
244.1SRV
84.1TBA
383.4SAP
124.1TBA
300.8TFA
345.4TFC
384.8AMH22 0864
2DAGS
383.4SSS
0MWL
84.1TBA
249TF
34.8TFC
383.4SRV
384.8MGOCOCKROACHES IN MANHOLE
37.8TBA
352.9TFA
0MGOCOCKROACHES IN MANHOLE
76.2TFC
2SSS
18.7TBA
228.5TFA
383.4DAGS
292.7TFC

Properties (6)

additional_info
SC365131
custom_field_two
2
customer
LACSD
datetime
2018-10-10T22:55:32-07:00
documentation
PRO PIPE
is_lateral_inspection
false